Introduction
ZEUS presents Isolators, IST-D (iSignalTrans) is user configurable using our iSignalwin software on your PC/notebook or our dedicated handheld programmer. The easy to use iSignalwin software is available free from your supplier or can be downloaded from our web site and should be used in conjunction with the URC-1020 USB cable which incorporates an interface converter necessary for communications. The IST-D transmitter can be configured without any loop or power connected making it easy to configure in the workshop before installation.

Feature
  1. Programmable for various input signals and measuring ranges.
  2. Configurable without Loop or Power Connected.
  3. Din Rail Mount.

Inputs
  1. Resistance thermometer (PT100 / RTD)
  2. Thermocouple (J,K,T,E,B,R,S,N,C)
  3. Also available for Voltage, Current and mV

Output
  1. 2-wire loop-power technology, 4 to 20 mA or 20 to 4 mA analog output.
  2. High accuracy in total ambient temperature range.
  3. Sensor break fault signal level pre-setable.

Specification
Product Isolators
Model No. IST-D
Input • Thermocouple (T/C) : industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90).
• Pt100: Excitation 180uA. 2 or 3 wire connection (ITS-90 α=0.00385).
• Upto 100 kbps under 4,000 ft. (1.2 km)
• Voltage: -60mVdc to 60mVdc or –10Vdc to 10Vdc.
• Current : 0-24mAdc
Accuracy Refer to Table 1 Input Signal
A/D Resolution 16 bits
Input Sampling Rate <200ms
Power supply DC 10 to 36V
Max. Load (V-10)/0.02 ( Ω )
Output Resolution 0.6 µ A(15 bits)
Output Resolution time <200ms
Common Mode Rejection Ratio(CMRR) >80dB
Electromagnetic compatibility En 50081-2, En 50082-2
Galvanic isolation 4 KV. between input and output
Operating Temperature -40 to 85 ° C
Humidity 0 to 90% RH
Dimension 75mm(W)x87mm(H)x18.5mm(D)
Input signal Code Maximum Range Accuracy
Thermocouple J J -50 to 1000 ° C (-58 to 1832 ° F ) ± 1 ° C
Thermocouple K K -50 to 1370 ° C (-58 to 2498 ° F ) ± 1 ° C
Thermocouple T T -270 to 400 ° C (-454 to 752 ° F ) ± 1 ° C
Thermocouple E E -50 to 960 ° C (-58 to 1760 ° F ) ± 1 ° C
Thermocouple B B 0 to 1750 ° C (32 to 3182 ° F ) ± 2 ° C (Note1)
Thermocouple R R -50 to 1750 ° C (-58 to 3182 ° F ) ± 2 ° C
Thermocouple S S -50 to 1750 ° C (-58 to 3182 ° F ) ± 2 ° C
Thermocouple N N -50 to 1300 ° C (-58 to 2372 ° F ) ± 2 ° C
Thermocouple C C -50 to 1800 ° C (-58 to 3272 ° F ) ± 2 ° C
Pt100 D -200 to 600 ° C (-328 to 1112 ° F ) ± 0.2 ° C
mV L -60mVto 60mV ± 0.01m V
Voltage (Note2) V -10 to 10Vdc ± 1m V
Current (Note2) M 0 to 24mAdc ± 10 µ A

Note: Technical specifications are subject to change without prior information